+86 18068001229 Mea hoʻololi Alloy Amorphous a me ka Mea hoʻololi Steel Silicon
Ua ʻike anei ʻoe i ka ʻokoʻa ma waena o Mea hoʻololi Alloy Amorphousa me nā mea hoʻololi kila silicon maʻamau? Ma ke ʻano he mea hana mea hoʻololi me 15+ mau makahiki o ka ʻike, wehewehe ʻo JZP i nā ʻokoʻa ma waena o kēia mau ʻano mea hoʻololi ʻelua. ʻAʻole ia he ʻokoʻa wale nō i nā mea; he kaua ʻenehana ia ma waena o ka pono o ka ikehu, ke kumukūʻai, a me nā ʻano e hiki mai ana.
ʻO ka Amorphous Alloy VS. ka mea hoʻololi maʻamau
Mea hoʻololi kila silikona maʻamau
He mau ʻiʻo ko nā mea hoʻololi maʻamau i hana ʻia me nā pepa kila silicon i ʻōwili anu ʻia, i hoʻonohonoho ʻia me ka palaoa, nona nā ʻātoma i hoʻonohonoho ʻia i loko o kahi ʻano crystalline maʻemaʻe a maʻamau.
ʻO kēia hoʻonohonoho pono ʻana e hopena i ke kū'ē magnetic haʻahaʻa loa i ka wā e magnetized ai ma ke kuhikuhi ʻōwili, e hopena ana i ka hana maikaʻi loa. Eia nō naʻe, he crystalline maoli nō lākou, a hoʻopau ka magnetization i ka ikehu, e hana ana i nā "hysteresis losses." Eia kekahi, he mānoanoa kekahi o nā pepa kila silicon, a ʻo nā kahua magnetic ʻokoʻa e hoʻoulu ai i nā "eddy current losses" i loko o lākou, e alakaʻi ana i nā "eddy current losses," i ʻike ʻia ʻo "iron losses."
Mea hoʻololi Alloy Amorphous
ʻO ke kumu o kahi mea hoʻololi alloy amorphous ua hana ʻia me ka lipine amorphous, i ʻike ʻia hoʻi ʻo "metallic glass." He chaotic a hoʻoponopono ʻole kona hoʻonohonoho atomika. Hoʻokumu ʻia kēia ʻano ma ka hoʻomaʻalili wikiwiki ʻana i kahi heheʻe wela kiʻekiʻe loa ma ka wikiwiki o nā miliona degere i kekona, kahi hana kū hoʻokahi. Hoʻemi nui kēia maʻi atomika lōʻihi i nā pohō hysteresis; ʻo kona mānoanoa lahilahi loa a me ke kū'ē kiʻekiʻe e hoʻemi hou aku i nā pohō o ke au eddy.
Hoʻohālikelike Hana
| Ana Hoʻohālikelike | Mea hoʻololi Alloy Amorphous
| Mea hoʻololi kila silikona maʻamau
| Ka Nānā ʻana a me ka Wehewehe ʻana
|
| Nā Pohō Koʻikoʻi
| Haʻahaʻa Loa
| Kiʻekiʻe
| ʻO ka awelika o nā pohō kaumaha ʻole, he 60%-80% ka haʻahaʻa ma mua o nā mea hoʻololi kila silicon S13/S14 like.
|
| Au ʻole-kaumaha
| Liʻiliʻi
| Nui
| Hiki ke hoʻemi ʻia ke au me ka ʻole o ke kaumaha ma kahi o 40%-80%, ʻo ia hoʻi ka emi ʻana o ka hopena o ka mana reactive ma ka grid a me ka emi ʻana o nā pohō laina.
|
| Pae Hana Ikehu
| Kiʻekiʻe Loa
| Kiʻekiʻe
| Hoʻokō maʻalahi nā mea hoʻololi amorphous i ke kūlana pono ikehu Class I aupuni, e hōʻike ana i ka maikaʻi loa o ka ikehu i hoʻohālikelike ʻia me nā mea hoʻololi kila silicon (ʻo ia hoʻi ʻo Class II a i ʻole Class III).
|
| Kumukūʻai Hana
| Kiʻekiʻe
| Haʻahaʻa iki
| He pipiʻi, paʻakikī, a palupalu hoʻi ke kaula hao amorphous, a he paʻakikī ke kaʻina hana ʻokiʻoki a me ka annealing, e hopena ana i nā kumukūʻai hana he 20%-35% kiʻekiʻe ma mua o ke kila silicon o ka mana like. ʻO kēia kona hemahema nui loa.
|
| Ikaika Mekanika
| Haʻahaʻa
| Kiʻekiʻe | He paʻakikī a palupalu ke kaula hao amorphous, me ka pale ʻole i ka haʻalulu a me ka haʻalulu. Pono e mālama pono i ka wā e lawe ʻia ai, e hoʻokomo ʻia ai, a me ka haʻalulu pōkole. ʻOi aku ka paʻakikī o ka pepa kila Silicon a ʻoi aku ka maikaʻi o ke kūpaʻa ʻana i ka hopena.
|
| Ka nui o ka flux magnetic hana
| Haʻahaʻa (1.3-1.5T)
| Kiʻekiʻe (1.6-1.8T)
| He haʻahaʻa ka saturation magnetic flux density o nā amorphous alloys, ʻo ia hoʻi, pono kahi ʻāpana ʻāpana nui o ke kumu ma ka mana like, kahi e alakaʻi ai i ka hoʻonui iki ʻana o ka nui a me ke kaumaha o ka mea hoʻololi.
|
| Walaʻau Hana
| Kiʻekiʻe iki
| Haʻahaʻa
| ʻOi aku ka ʻike ʻia o ka hopena magnetostrictive (kahi loli liʻiliʻi i ka nui o ka mea ke magnetized) o nā alloys amorphous ma mua o nā pepa kila silicon, e hopena ana i kahi hum kiʻekiʻe iki aʻe (ma kahi o 2-5 dB kiʻekiʻe aʻe) i ka wā o ka hana. Pono paha ka lawelawe kūikawā ma nā wahi i pili i ka walaʻau.
|
| Hana Kaiapuni
| Maikaʻi loa
| Maikaʻi loa | ʻO ka pohō haʻahaʻa loa me ka ʻole o ke kaumaha, ʻo ia hoʻi ka mālama ʻana i ka ikehu nui ma ke ola holoʻokoʻa (20-30 mau makahiki), like me ka hōʻemi ʻana i nā hoʻokuʻu kalapona e kekahi mau tona a i ʻole he ʻumi mau tona. |
Nā mea hoʻololi kila silicon maʻamau: Hoʻopukapuka mua haʻahaʻa, akā kiʻekiʻe ke kumukūʻai uila hana. Loaʻa ko lākou pohō ukana ʻole i 24 mau hola o ka lā, e hoʻopau mau ana i ka uila inā pili ka mea hoʻololi i ka pūnaewele.
Nā mea hoʻololi alloy amorphous: Hoʻopukapuka mua kiʻekiʻe, akā haʻahaʻa loa nā kumukūʻai uila hana. ʻAʻole paha e mālama ʻia ko lākou ikehu i hoʻokahi lā, akā ma luna o ko lākou ola holoʻokoʻa (20-30 mau makahiki), hiki ke nui loa ka mālama ʻana.
No nā ʻoihana me ka nui o nā Mea Hoʻololi Hoʻolahaa me nā mea hoʻohaʻahaʻa haʻahaʻa (e like me nā ʻoihana pūnaewele mana, nā kikowaena ʻikepili, a me nā hale kalepa nui), he mea hoihoi loa nā pono waiwai o nā mea hoʻololi amorphous.